Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7213 Hickory Rd

Approved

Filed Jul 17, 2025 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Jul 17, 2025
Assembly type
PVB
Serial number
K521234
Size
1
Test gauge serial
G-2124
Gauge calibration date
Dec 8, 2024
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-92-01128
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7213 Hickory Rd
Owner: Hayden Nguyen
Parcel 014-92-01128