Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8230 Sycamore Ln

Approved

Filed Jul 7, 2026 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Jul 7, 2026
Assembly type
RP
Serial number
A414236
Size
3/4
Test gauge serial
G-4077
Gauge calibration date
Jun 5, 2026
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-87-01221
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

8230 Sycamore Ln
Owner: Rowan Ellery
Parcel 014-87-01221