Backflow assembly test · 2080 Pine Knoll Dr
ApprovedFiled Jun 14, 2024 by Reese Stroud, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Jun 14, 2024
- Assembly type
- PVB
- Serial number
- Z517850
- Size
- 1
- Test gauge serial
- G-8604
- Gauge calibration date
- Nov 27, 2023
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-92-01215
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.