Backflow assembly test · 5499 Fox Run Dr
ApprovedFiled Feb 10, 2026 by Reese Stroud, Evergreen Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Feb 10, 2026
- Assembly type
- PVB
- Serial number
- Z439281
- Size
- 3/4
- Test gauge serial
- G-6821
- Gauge calibration date
- Oct 14, 2025
- Check valve 1
- 3.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-43-01082
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.