Backflow assembly test · 5688 Cedar Hollow Ct

Approved

Filed May 19, 2024 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone

Report

Date of service
May 19, 2024
Assembly type
RP
Serial number
B601521
Size
3/4
Test gauge serial
G-9722
Gauge calibration date
Mar 10, 2024
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-96-01314
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5688 Cedar Hollow Ct
Owner: Rowan Pruitt
Parcel 014-96-01314