Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4057 Meadow Lark Way

Approved

Filed Aug 21, 2024 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Aug 21, 2024
Assembly type
RP
Serial number
B910512
Size
3/4
Test gauge serial
G-1611
Gauge calibration date
Nov 2, 2023
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-55-01041
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4057 Meadow Lark Way
Owner: Riley Danner
Parcel 014-55-01041