Backflow assembly test · 2235 Laurel Ct
ApprovedFiled May 19, 2024 by Shawn Hollins, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- May 19, 2024
- Assembly type
- RP
- Serial number
- K142478
- Size
- 3/4
- Test gauge serial
- G-8976
- Gauge calibration date
- May 18, 2023
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-57-01143
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2235 Laurel Ct
Owner: Quinn Vance
Parcel 013-57-01143