Backflow assembly test · 9616 Laurel Dr
Needs reviewFiled Nov 17, 2026 by Casey Kessler, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Nov 17, 2026
- Assembly type
- DC
- Serial number
- W139869
- Size
- 1
- Test gauge serial
- G-1861
- Gauge calibration date
- May 31, 2026
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-40-01105
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.