Backflow assembly test · 9610 Quarry Rd

Approved

Filed Oct 18, 2026 by Shawn Hollins, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Oct 18, 2026
Assembly type
RP
Serial number
W478358
Size
1
Test gauge serial
G-3099
Gauge calibration date
Jan 29, 2026
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-31-01241
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

9610 Quarry Rd
Owner: Hayden Marsh
Parcel 013-31-01241