Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 663 Orchard Rd

Approved

Filed Sep 22, 2025 by Cameron Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Sep 22, 2025
Assembly type
RP
Serial number
A351130
Size
3/4
Test gauge serial
G-1584
Gauge calibration date
Jan 18, 2025
Check valve 1
6.2 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-92-01216
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

663 Orchard Rd
Owner: Quinn Kessler
Parcel 013-92-01216