Backflow assembly test · 4318 Meadow Lark Way
ApprovedFiled Jun 26, 2025 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Jun 26, 2025
- Assembly type
- RP
- Serial number
- A144215
- Size
- 1
- Test gauge serial
- G-6374
- Gauge calibration date
- Apr 2, 2025
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-44-01275
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4318 Meadow Lark Way
Owner: Casey Vance
Parcel 013-44-01275