Backflow assembly test · 9897 Fox Run Trl
ApprovedFiled Jun 22, 2024 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Jun 22, 2024
- Assembly type
- PVB
- Serial number
- B123230
- Size
- 1
- Test gauge serial
- G-9867
- Gauge calibration date
- Dec 8, 2023
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-23-01323
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9897 Fox Run Trl
Owner: Rowan Brandt
Parcel 013-23-01323