Backflow assembly test · 3404 Pine Knoll Ln

Approved

Filed Oct 14, 2024 by Cameron Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Oct 14, 2024
Assembly type
RP
Serial number
K785094
Size
1
Test gauge serial
G-4340
Gauge calibration date
Dec 21, 2023
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-51-01355
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3404 Pine Knoll Ln
Owner: Hayden Marsh
Parcel 013-51-01355