Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3404 Pine Knoll Ln

Approved

Filed Oct 18, 2023 by Casey Kessler, Northstar Backflow Testing · filed from phone

Report

Date of service
Oct 18, 2023
Assembly type
RP
Serial number
K785094
Size
1
Test gauge serial
G-2243
Gauge calibration date
Aug 13, 2022
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-51-01355
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

3404 Pine Knoll Ln
Owner: Hayden Marsh
Parcel 013-51-01355