← Backflow review queue
Backflow assembly test · 9560 Orchard Trl
ApprovedFiled Sep 17, 2025 by Shawn Hollins, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Sep 17, 2025
- Assembly type
- DC
- Serial number
- B537878
- Size
- 3/4
- Test gauge serial
- G-2080
- Gauge calibration date
- Jun 27, 2025
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-25-01027
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9560 Orchard Trl
Owner: Jamie Marsh
Parcel 013-25-01027