Backflow assembly test · 8977 Turkey Hill Rd

Approved

Filed Sep 28, 2026 by Casey Kessler, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Sep 28, 2026
Assembly type
DC
Serial number
A436380
Size
3/4
Test gauge serial
G-5970
Gauge calibration date
Nov 3, 2025
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-18-01204
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8977 Turkey Hill Rd
Owner: Morgan Kessler
Parcel 005-18-01204