Backflow assembly test · Riverside Diner

Approved

Filed Dec 13, 2024 by Cameron Kessler, Heritage Backflow Testing · filed from phone

Report

Date of service
Dec 13, 2024
Assembly type
DC
Serial number
A465444
Size
2
Test gauge serial
G-4765
Gauge calibration date
Aug 30, 2024
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-53-01329
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9668 Pine Knoll Way
Owner: Lindqvist Holdings LLC
Parcel 005-53-01329