Arapahoe County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Grill

Approved

Filed Nov 11, 2026 by Casey Kessler, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Nov 11, 2026
Assembly type
RP
Serial number
A635465
Size
1 1/2
Test gauge serial
G-8001
Gauge calibration date
May 9, 2026
Check valve 1
5.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-75-01313
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

2782 Spring Branch Way
Owner: Kessler Holdings LLC
Parcel 005-75-01313