Arapahoe County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Elementary School

Approved

Filed Mar 20, 2026 by Quinn Harlow, Heritage Plumbing & Backflow · filed from phone

Report

Date of service
Mar 20, 2026
Assembly type
RP
Serial number
K645319
Size
4
Test gauge serial
G-5569
Gauge calibration date
Oct 24, 2025
Check valve 1
5.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-16-01158
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.