← Backflow review queue
Backflow assembly test · Golden Elementary School
ApprovedFiled Mar 21, 2025 by Quinn Harlow, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Mar 21, 2025
- Assembly type
- RP
- Serial number
- K645319
- Size
- 4
- Test gauge serial
- G-4030
- Gauge calibration date
- Jan 5, 2025
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 005-16-01158
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7330 Meadow Lark Dr
Owner: Ellery Holdings LLC
Parcel 005-16-01158