Arapahoe County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Elementary School

Approved

Filed Mar 21, 2025 by Quinn Harlow, Heritage Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Mar 21, 2025
Assembly type
RP
Serial number
K645319
Size
4
Test gauge serial
G-4030
Gauge calibration date
Jan 5, 2025
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
3.3 psid
Relief valve opened at
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 005-16-01158
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7330 Meadow Lark Dr
Owner: Ellery Holdings LLC
Parcel 005-16-01158