Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5448 Turkey Hill Trl

Approved

Filed Jun 27, 2024 by Reese Harlow, Clearwater Plumbing & Backflow · filed from phone

Report

Date of service
Jun 27, 2024
Assembly type
RP
Serial number
K415318
Size
3/4
Test gauge serial
G-9843
Gauge calibration date
Dec 11, 2023
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-66-01267
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

5448 Turkey Hill Trl
Owner: Avery Okafor
Parcel 001-66-01267