← Backflow review queue
Backflow assembly test · Maple Leaf Self Storage
ApprovedFiled Jul 6, 2025 by Logan Ramirez, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 6, 2025
- Assembly type
- RP
- Serial number
- W197062
- Size
- 1 1/2
- Test gauge serial
- G-9333
- Gauge calibration date
- Dec 17, 2024
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-13-01205
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6056 Cedar Hollow Rd
Owner: Whitcomb Holdings LLC
Parcel 001-13-01205