Backflow assembly test · 6151 Old Church Ln
ApprovedFiled Oct 22, 2025 by Rowan Marsh, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 22, 2025
- Assembly type
- RP
- Serial number
- A351461
- Size
- 1
- Test gauge serial
- G-9303
- Gauge calibration date
- May 28, 2025
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-86-01012
- Readings in range, no flags
- Result: passing. Next due date resets when approved.