Backflow assembly test · Station Self Storage
ApprovedFiled Aug 4, 2026 by Quinn Fairley, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 4, 2026
- Assembly type
- RP
- Serial number
- B784214
- Size
- 1 1/2
- Test gauge serial
- G-4714
- Gauge calibration date
- Nov 8, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2 psid
- Relief valve opened at
- 3.4 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-22-01128
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9799 Cedar Hollow Ln
Owner: Vance Holdings LLC
Parcel 001-22-01128