Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Animal Hospital

Approved

Filed Jul 30, 2025 by Reese Harlow, Clearwater Plumbing & Backflow · filed from phone

Report

Date of service
Jul 30, 2025
Assembly type
RP
Serial number
A667205
Size
1 1/2
Test gauge serial
G-2727
Gauge calibration date
Feb 6, 2025
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-80-01317
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

4788 Pine Knoll Way
Owner: Kessler Holdings LLC
Parcel 001-80-01317