← Backflow review queue
Backflow assembly test · 8357 Pine Knoll Trl
ApprovedFiled Jan 12, 2025 by Quinn Fairley, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 12, 2025
- Assembly type
- RP
- Serial number
- B840766
- Size
- 1
- Test gauge serial
- G-3393
- Gauge calibration date
- Oct 12, 2024
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-47-01105
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8357 Pine Knoll Trl
Owner: Cameron Benton
Parcel 001-47-01105