Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Elementary School

Approved

Filed Apr 18, 2025 by Reese Harlow, Clearwater Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Apr 18, 2025
Assembly type
RP
Serial number
B576249
Size
2
Test gauge serial
G-1989
Gauge calibration date
Jun 24, 2024
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
1.1 psid
Relief valve opened at
3.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-21-01141
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9036 Hickory Trl
Owner: Fairley Holdings LLC
Parcel 001-21-01141