Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Diner

Approved

Filed Dec 25, 2024 by Logan Ramirez, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Dec 25, 2024
Assembly type
RP
Serial number
K227686
Size
1
Test gauge serial
G-6237
Gauge calibration date
Sep 3, 2024
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-94-01304
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8702 Orchard Dr
Owner: Harlow Holdings LLC
Parcel 001-94-01304