Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Taqueria

Approved

Filed May 23, 2025 by Rowan Marsh, Valley Plumbing & Backflow · filed from phone

Report

Date of service
May 23, 2025
Assembly type
RP
Serial number
Z829068
Size
2
Test gauge serial
G-1293
Gauge calibration date
Jan 29, 2025
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-88-01017
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4463 Sycamore Dr
Owner: Ashby Holdings LLC
Parcel 001-88-01017