Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Taqueria

Approved

Filed May 23, 2024 by Quinn Fairley, Valley Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
May 23, 2024
Assembly type
RP
Serial number
Z829068
Size
2
Test gauge serial
G-8788
Gauge calibration date
Apr 13, 2024
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-88-01017
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4463 Sycamore Dr
Owner: Ashby Holdings LLC
Parcel 001-88-01017