Adams County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 300 Spring Branch Trl

Approved

Filed Jun 20, 2024 by Quinn Fairley, Valley Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jun 20, 2024
Assembly type
RP
Serial number
B334263
Size
3/4
Test gauge serial
G-8783
Gauge calibration date
Jan 27, 2024
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
1.5 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-99-01249
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

300 Spring Branch Trl
Owner: Logan Ramirez
Parcel 001-99-01249