Yolo County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7370 Cedar Hollow Ct

Approved

Filed Feb 10, 2025 by Casey Ramirez, Ridge Backflow Testing · filed from phone

Report

Date of service
Feb 10, 2025
Assembly type
RP
Serial number
A954465
Size
1
Test gauge serial
G-9352
Gauge calibration date
Dec 16, 2023
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
1.1 psid
Relief valve opened at
4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 113-70-01307
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7370 Cedar Hollow Ct
Owner: Sam Kessler
Parcel 113-70-01307