Backflow assembly test · 7227 Sycamore Dr
ApprovedFiled Oct 11, 2024 by Riley Lindqvist, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Oct 11, 2024
- Assembly type
- DC
- Serial number
- Z176595
- Size
- 3/4
- Test gauge serial
- G-7001
- Gauge calibration date
- Jul 28, 2024
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 113-23-01287
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.