Backflow assembly test · 979 Laurel Ct
ApprovedFiled Nov 19, 2024 by Emerson Wexler, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Nov 19, 2024
- Assembly type
- RP
- Serial number
- W543576
- Size
- 3/4
- Test gauge serial
- G-3113
- Gauge calibration date
- Feb 10, 2024
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 4.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-42-01263
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.