Backflow assembly test · 9257 Quarry Dr
ApprovedFiled May 27, 2025 by Shawn Stroud, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- May 27, 2025
- Assembly type
- RP
- Serial number
- Z917611
- Size
- 3/4
- Test gauge serial
- G-1747
- Gauge calibration date
- Aug 8, 2024
- Check valve 1
- 8.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-15-01035
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9257 Quarry Dr
Owner: Reese Kessler
Parcel 111-15-01035