Backflow assembly test · 9672 Mill Creek Way
ApprovedFiled Nov 9, 2023 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Nov 9, 2023
- Assembly type
- RP
- Serial number
- Z108836
- Size
- 3/4
- Test gauge serial
- G-8251
- Gauge calibration date
- Aug 6, 2023
- Check valve 1
- 3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-18-01007
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9672 Mill Creek Way
Owner: Blake Danner
Parcel 111-18-01007