Backflow assembly test · 7222 Sycamore Trl
ApprovedFiled Oct 5, 2026 by Cameron Whitcomb, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Oct 5, 2026
- Assembly type
- DC
- Serial number
- W798981
- Size
- 3/4
- Test gauge serial
- G-7534
- Gauge calibration date
- Aug 28, 2026
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-65-01136
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.