← Backflow review queue
Backflow assembly test · 3977 Quarry Ln
ApprovedFiled Jul 12, 2024 by Cameron Whitcomb, Evergreen Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 12, 2024
- Assembly type
- RP
- Serial number
- Z441766
- Size
- 1
- Test gauge serial
- G-1278
- Gauge calibration date
- Dec 10, 2023
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-85-01276
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3977 Quarry Ln
Owner: Quinn Benton
Parcel 111-85-01276