Backflow assembly test · 3558 Ridgeview Dr
ApprovedFiled Apr 23, 2026 by Cameron Whitcomb, Evergreen Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 23, 2026
- Assembly type
- RP
- Serial number
- K461415
- Size
- 1
- Test gauge serial
- G-6955
- Gauge calibration date
- Nov 5, 2025
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 4.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 111-34-01203
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.