Backflow assembly test · 1077 Orchard Trl
ApprovedFiled May 10, 2026 by Jordan Brandt, Summit Backflow Testing · filed from phone
Report
- Date of service
- May 10, 2026
- Assembly type
- RP
- Serial number
- A630752
- Size
- 3/4
- Test gauge serial
- G-6055
- Gauge calibration date
- Aug 26, 2025
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-85-01296
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1077 Orchard Trl
Owner: Riley Nguyen
Parcel 107-85-01296