Tulare County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7751 Spring Branch Ln

Approved

Filed May 2, 2026 by Parker Fairley, Patriot Backflow Testing · filed from phone

Report

Date of service
May 2, 2026
Assembly type
RP
Serial number
A816228
Size
1
Test gauge serial
G-3845
Gauge calibration date
Jul 30, 2025
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-15-01157
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7751 Spring Branch Ln
Owner: Jamie Marsh
Parcel 107-15-01157