← Backflow review queue
Backflow assembly test · 7004 Turkey Hill Rd
ApprovedFiled Oct 26, 2024 by Avery Stroud, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 26, 2024
- Assembly type
- DC
- Serial number
- A771027
- Size
- 1
- Test gauge serial
- G-7270
- Gauge calibration date
- Jun 27, 2024
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-55-01144
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7004 Turkey Hill Rd
Owner: Cameron Ellery
Parcel 107-55-01144