Backflow assembly test · Two Rivers Animal Hospital
ApprovedFiled Nov 24, 2023 by Avery Stroud, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 24, 2023
- Assembly type
- RP
- Serial number
- B969517
- Size
- 2
- Test gauge serial
- G-9400
- Gauge calibration date
- May 2, 2023
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-65-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2124 Cedar Hollow Ct
Owner: Benton Holdings LLC
Parcel 107-65-01239