Backflow assembly test · 6485 Pine Knoll Trl
ApprovedFiled Sep 18, 2025 by Parker Fairley, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Sep 18, 2025
- Assembly type
- RP
- Serial number
- K495924
- Size
- 3/4
- Test gauge serial
- G-8216
- Gauge calibration date
- Feb 24, 2025
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-70-01322
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6485 Pine Knoll Trl
Owner: Hayden Vance
Parcel 107-70-01322