← Backflow review queue
Backflow assembly test · 6485 Pine Knoll Trl
ApprovedFiled Aug 22, 2023 by Avery Stroud, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 22, 2023
- Assembly type
- RP
- Serial number
- K495924
- Size
- 3/4
- Test gauge serial
- G-7919
- Gauge calibration date
- Dec 12, 2022
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 107-70-01322
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6485 Pine Knoll Trl
Owner: Hayden Vance
Parcel 107-70-01322