Tulare County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Medical Offices

Filed Nov 20, 2026 by Parker Vance, Summit Backflow Testing · filed from phone

Report

Date of service
Nov 20, 2026
Assembly type
RP
Serial number
Z907935
Size
2
Test gauge serial
G-6653
Gauge calibration date
Oct 16, 2026
Check valve 1
9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 107-21-01200
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

6516 Sycamore Trl
Owner: Nguyen Holdings LLC
Parcel 107-21-01200