Backflow assembly test · 2806 Fox Run Ct
ApprovedFiled Jul 9, 2025 by Drew Okafor, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 9, 2025
- Assembly type
- RP
- Serial number
- A824283
- Size
- 3/4
- Test gauge serial
- G-8942
- Gauge calibration date
- May 7, 2025
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-15-01097
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.