← Backflow review queue
Backflow assembly test · 6049 Turkey Hill Rd
ApprovedFiled Oct 11, 2025 by Alex Kessler, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 11, 2025
- Assembly type
- RP
- Serial number
- B691190
- Size
- 1
- Test gauge serial
- G-8772
- Gauge calibration date
- Aug 13, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 2.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-42-01070
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6049 Turkey Hill Rd
Owner: Quinn Fairley
Parcel 097-42-01070