Backflow assembly test · Two Rivers Car Wash
ApprovedFiled Nov 11, 2025 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 11, 2025
- Assembly type
- RP
- Serial number
- Z579178
- Size
- 2
- Test gauge serial
- G-1267
- Gauge calibration date
- Mar 24, 2025
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-42-01250
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.