Backflow assembly test: 2200 Turkey Hill Way

Approved

Filed Mar 8, 2026 by Alex Kessler, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 8, 2026
Assembly type
RP
Serial number
K440439
Size
1
Test gauge serial
G-6330
Gauge calibration date
Nov 8, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Kessler, current on the service date
  • All required fields present
  • Address matches parcel 097-56-01058
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2200 Turkey Hill Way
Owner: Morgan Stroud
Parcel 097-56-01058